Knauf Acoustical Board Smooth with ECOSE® Technology
Description
Knauf Acoustical Board Smooth with ECOSE Technology is a thermal
and acoustical insulation product bonded with ECOSE Technology.
Color
ECOSE Technology gives the
product its unique brown color.
ECOSE
Technology
ECOSE Technology is a revolutionary new binder chemistry that
makes Knauf Insulation products even more sustainable than ever. It
is based on rapidly renewable bio-based materials rather than
nonrenewable petroleum-based chemicals traditionally used in fiber
glass insulation products. ECOSE Technology reduces binder embodied
energy and does not contain phenol, formaldehyde, acrylics or
artificial colors.
Application
Knauf Acoustical Board Smooth with ECOSE Technology is a
versatile product for thermal and acoustical applications such as
office partitions, ceiling panels, interior panels and sound
baffles.
Features and
Benefits
Density and Size
Availability
Knauf Acoustical Board Smooth with ECOSE Technology is available
in the densities and sizes required by panel and ceiling
manufacturers. Special items not shown on the price and data sheet
can be made based on our process capability.
Surface
Smoothness
One surface is smooth which allows for flatness and
uniformity.
Precision
Tolerances
Tolerances are +/- 1/16" (1.59 mm) for thickness and +/- 1/8"
(3.18 mm)for width and length.
Fabrication
The board is suitable for machining.
Noise Reduction
Excellent sound absorption characteristics, an important benefit
for today’s office and interiors.
Indoor Air
Quality
Certified for indoor air quality as a low emitting product by
The GREENGUARD Environmental Institute to both the GREENGUARD
Certification ProgramSM and the more stringent GREENGUARD Children
and SchoolsSM standard.
Sustainability
- Carbon-negative - meaning: Knauf insulation products used for
thermal insulating purposes recover the energy that it took to make
them in just hours or a few days, depending on the application.
Once installed, the product continues to save energy and reduce
carbon generation as long as it is in place.
- Fiber glass insulation with ECOSE
Technology contains three primary ingredients:
Sand, one of the world’s
most abundant and renewable resources
Post-consumer recycled
bottle glass
ECOSE Technology which
reduces binder embodied energy by up to 70%
Packaging
Available on pallets and in cartons. See Packaging table
below.
Specification
Compliance
In U.S.:
- ASTM C 612; Type IA and Type IB
- GREENGUARD Children & SchoolsSM
Certification
- California Title 24
- HH-I-558C; Form A, Class 1 and Class
2
- NFPA 90A and 90B
In Canada:
- CAN/ULC S102-M88
- CGSB 51-GP-10M
Technical Data
Surface Burning
Characteristics (UL Classified)
Does not exceed 25 Flame Spread, 50 Smoke Developed when tested
in accordance with ASTM E 84, CAN/ULC S102-M88, NFPA 90A and 90B,
NFPA 255 and UL 723.
Temperature Range (ASTM C
411)
Operating temperatures from 0°F to 450°F (-18°C to 232°C) up to
4" product thickness
Corrosiveness (ASTM C
665)
Does not accelerate corrosion on steel, copper or aluminum.
Corrosion (ASTM C
1617)
The corrosion rate in mils/yr will not exceed that of the 1 ppm
chloride solution.
Shrinkage (ASTM C
356)
Less than 0.3% linear shrinkage.
Mold Growth (ASTM C
1338
Does not promote growth.
Water Vapor Sorption (ASTM C
1104)
Less than 5% by weight.
Odor (ASTM C
1304)
Not objectionable.
Low Emitting
Certified for indoor air quality as a low emitting product by
the GREENGUARD Environmental Institute.
Product
Availability
1. Stock items are listed. The
remainder of the product line is made-to-order.
2. Acoustical Board Smooth is
skidded smooth on one side except for 1/2" thick which is
bisected
as noted below.
3. Product tolerances:+/- 1/16"
(1.59 mm) thickness; +/- 1/8" (3.18 mm) width and length.
4. It is recommended that
Acoustical Board Smooth be sampled and evaluated prior to
ordering.
5. For requirements not listed,
contact your Knauf Insulation sales representative.
Fiber Glass and
Mold
Fiber glass insulation will not sustain mold growth. However,
mold can grow on almost any material when it becomes wet and
contaminated. Carefully inspect any insulation that has been
exposed to water. If it shows any sign of mold it must be
discarded. If the material is wet but shows no evidence of mold, it
should be dried rapidly and thoroughly. If it shows signs of facing
degradation from wetting, it should be replaced. Air handling
insulation used in the air stream must be discarded if exposed to
water.
Notes
The chemical and physical properties of Knauf Acoustical Board
Smooth with ECOSE Technology represent typical average values
determined in accordance with accepted test methods. The data is
subject to normal manufacturing variations. The data is supplied as
a technical service and is subject to change without notice.
References to numerical flame spread ratings are not intended to
reflect hazards presented by these or any other materials under
actual fire conditions. Check with your Knauf Insulation sales
representative to assure information is current.
Knauf
Acoustical Board Smooth Insulation with ECOSE Technology products
are certified for indoor air quality as a low emitting product by
The GREENGUARD Environmental Institute to both the GREENGUARD
Certification ProgramSM and the more stringent GREENGUARD for
Children and SchoolsSM standard. www.greenguard.org. The GREENGUARD
INDOOR AIR QUALITY CERTIFIED Mark is a registered certification
mark used under license through the GREENGUARD Environmental
Institute.
SOUND ABSORPTION COEFFICIENTS
(ASTM C 423, Type A Mounting)
|
|
|
Octave Band Center
Frequency (cycles/sec.)
|
|
Density
|
Thickness
|
125
|
250
|
500
|
1000
|
2000
|
4000
|
NRC
|
|
3.0 PCF (48
kg/m3)
|
1''
|
(25 mm)
|
.08
|
.23
|
.62
|
.88
|
.96
|
.99
|
.65
|
|
1½''
|
(38 mm)
|
.09
|
.39
|
.89
|
1.03
|
1.06
|
1.01
|
.85
|
|
2''
|
(51 mm)
|
.29
|
.65
|
1.11
|
1.13
|
1.06
|
1.03
|
1.00
|
|
3''
|
(76 mm)
|
.54
|
1.01
|
1.18
|
1.07
|
1.07
|
1.04
|
1.10
|
|
4.25 PCF (68
kg/m3)
|
1''
|
(25 mm)
|
.06
|
.24
|
.69
|
.99
|
1.05
|
1.02
|
.75
|
|
6.0 PCF (96
kg/m3)
|
1''
|
(25 mm)
|
.05
|
.26
|
.77
|
1.04
|
1.04
|
1.03
|
.80
|
|
1½''
|
(38 mm)
|
.13
|
.58
|
1.01
|
1.05
|
1.00
|
1.01
|
.90
|
|
2''
|
(51 mm)
|
.32
|
.81
|
1.08
|
1.06
|
1.03
|
1.04
|
1.00
|
THERMAL CONDUCTIVITY (ASTM C 177) @
75˚F Mean
|
Density
|
Thermal Conductivity
|
|
3.0 PCF (48
kg/m3)
|
0.23
|
|
4.25 PCF (64
kg/m3)
|
0.23
|
|
6.0 PCF (96
kg/m3)
|
0.22
|
FORMS
AVAILABLE
|
Density
|
Thickness
|
Width*
|
Length
|
Minimum
Release
|
|
3.0 PCF
(48 kg/m3)
|
1"
|
(25 mm)
|
24", 48"
(610 mm, 1219 mm)
|
48", 96", 120"
(1219 mm, 2438 mm,
3048 mm)
|
24 MSF
|
|
1½"
|
(38 mm)
|
16 MSF
|
|
2"
|
(51 mm)
|
12 MSF
|
|
3"
|
(76 mm)
|
8 MSF
|
|
4.25 PCF
(68 kg/m3)
|
½"
|
(13 mm)
|
36 MSF
|
|
1"
|
(25 mm)
|
18 MSF
|
|
1½"
|
(38 mm)
|
14 MSF
|
|
2"
|
(51 mm)
|
9 MSF
|
|
6.0 PCF
(96 kg/m3)
|
½"
|
(13 mm)
|
24 MSF
|
|
1"
|
(25 mm)
|
12 MSF
|
|
1½"
|
(38 mm)
|
9 MSF
|
|
2"
|
(51 mm)
|
6 MSF
|
PACKAGING AVAILABLE
| Product Dimensions |
Carton |
Pallet |
| 24" x 48" |
x |
|
| 48" x 96" |
x |
x |
| 48" x 120" |
x
|
x
|
| 48" x 144" |
|
x
|
| 49" x 97" |
|
x
|
| 49" x 121" |
|
x
|
| 49" x 145" |
|
|