Description
Knauf Elevated Temperature Panel 1000° with ECOSE®
Technology is a semi-rigid thermal insulation board (2.4 pcf, 38.4
kg/m3) bonded with ECOSE Technology.
ECOSE Technology
ECOSE Technology is a revolutionary new binder chemistry that
makes Knauf Insulation products even more sustainable than ever. It
is based on rapidly renewable bio-based materials rather than
nonrenewable petroleum-based chemicals traditionally used in fiber
glass insulation products. ECOSE Technology reduces binder embodied
energy and does not contain phenol, formaldehyde, acrylics or
artificial colors.
Application
Knauf Elevated Temperature Panel 1000° with ECOSE Technology
is suitable for use in industrial heating applications to 1000°F
(538°C), such as hightemperature panel systems for ducts and
precipitators, boilers, vessels and industrial ovens. It is ideal
for use in metal mesh blankets.
Features and Benefits
Excellent Thermal Properties
Low Installed Cost
- Lightweight.
- Easy to fabricate.
- Sizes up to 4' x 10' available.
Polybag and Sleeve Packaging
- Damage resistant.
- Reduces storage space.
Resilient Fiber Glass
- Maintains integrity at elevated temperatures.
Low Emitting
- Certified for indoor air quality as a low emitting product by
The GREENGUARD Environmental Institute to both the
GREENGUARD Certification ProgramSM and the more
stringent GREENGUARD Children and SchoolsSM
standard.
Sustainability
- Carbon negative: meaning Knauf insulation products used for
thermal insulating purposes recover the energy that it took to make
them in just hours or a few days, depending on the application.
Once installed, the product continues to save energy and reduce
carbon generation as long as it is in place.
Fiber glass insulation with ECOSE Technology
- contains three primary ingredients:
- Sand, one of the world’s most abundant and renewable
resources
- Post-consumer recycled bottle glass
- ECOSE Technology which reduces binder embodied energy by up to
70%
Specification Compliance
In U.S.:
- ASTM C 612; Type II and III
- GREENGUARD Indoor Air Quality Certified®
- GREENGUARD Children & SchoolsSM
- HH-I-558C; Form A, Class 1, 3
- USCG 164.109/17/0
In Canada:
- CAN/ULC S102-M88
- CGSB 51-GP-10M
Technical Data
Surface Burning Characteristics
- Does not exceed 25 Flame Spread, 50 Smoke Developed when tested
in accordance with ASTM E 84, CAN/ULC S102-M88, and UL 723.
Water Vapor Sorption (ASTM C 1104)
Corrosiveness (ASTM C 665)
- Will not accelerate corrosion of aluminum, steel or
copper.
Corrosion (ASTM C 1617)
- The corrosion rate in mils/yr will not exceed that of the 1 ppm
chloride solution.
Temperature Limit (ASTM C 411)
- Up to 1000°F (538°C) at a maximum recommended thickness of 6
inches.
Microbial Growth (ASTM C 1338)
- Does not promote or support the growth of mold, fungi or
bacteria.
Application and Specification Guidelines
Precautions
- During initial heat-up to operating temperatures above 350°F
(177°C), a slight odor and some smoke may be given off as a portion
of the bonding material used in the insulation begins to undergo a
controlled decomposition.
- If natural convection is not adequate in confined areas, forced
ventilation should be provided in order to protect against any
harmful fumes and vapors that might be generated.
Storage
- Protect material from water damage or other abuse. Cartons are
not designed for outside storage. Vacuum packaged material can be
stored outside if care is taken not to puncture the polybag.
Preparation
- Apply the product on clean, dry surfaces.
Application
- There is no heat-up cycle required for Knauf ET Panel
1000°.
- The product should be secured with welded pins and washers, or
studs and washers, and covered with sheet metal. An alternate
method entails covering the insulation with a metal mesh and
insulating cement, canvassing, and painting.
- Pins and washers shall be located a maximum of 4" (102 mm) from
each edge and spaced no greater than 16" (406 mm) on center.
- Care should be taken to avoid over compressing the insulation
with the retaining washer.
- Dual-layer installation with staggered joints is recommended
for applications where temperatures meet or exceed 550°F (288°C)
and designed thickness is over 3" (76 mm).
- When using the product at 1000°F (538°C), it is recommended
that no more than 6" (152 mm) thickness be used.
Caution
Fiber glass may cause temporary skin irritation. Wear
long-sleeved, loose-fitting clothing, head covering, gloves, and
eye protection when handling and applying material. Wash with soap
and warm water after handling. Wash work clothes separately and
rinse washer. A disposable mask designed for nuisance type dusts
should be used where sensitivity to dust and airborne particles may
cause irritation to the nose and throat.
Fiber Glass and Mold
Fiber glass insulation will not sustain mold growth. However,
mold can grow on almost any material when it becomes wet and
contaminated. Carefully inspect any insulation that has been
exposed to water. If it shows any sign of mold it must be
discarded. If the material is wet but shows no evidence of mold, it
should be dried rapidly and thoroughly. If it shows signs of facing
degradation from wetting, it should be replaced.
Notes
The chemical and physical properties of Knauf ET Panel 1000°
represent typical average values determined in accordance with
accepted test methods. The data is subject to normal manufacturing
variations. The data is supplied as a technical service and is
subject to change without notice. References to numerical flame
spread ratings are not intended to reflect hazards presented by
these or any other materials under actual fire conditions. Check
with your Knauf regional office to assure information is
current.
THERMAL EFFICIENCY (ASTM C 177)
|
Mean Temperature
|
Mean Temperature (SI)
|
k |
k (SI) |
| 100°F |
38°C |
.25 |
.036 |
| 200°F |
93°C |
.32 |
.046 |
| 300°F |
149°C |
.40 |
.058 |
| 400°F |
204°C |
.52 |
.075 |
| 500°F |
260°C |
.68 |
.098 |
STANDARD SIZES
|
Thickness |
Width |
Length |
| 1" (25 mm) |
24" (610 mm) |
48" and 96"
(1219 mm and 2438 mm) |
| 11/2" (38 mm) |
24" (610 mm) |
48" and 96"
(1219 mm and 2438 mm) |
| 2" (51 mm) |
24" (610 mm) |
48" and 96"
(1219 mm and 2438 mm) |
| 21/2" (64 mm) |
24" (610 mm) |
48" and 96"
(1219 mm and 2438 mm) |
| 3" (76 mm) |
24" (610 mm) |
48" and 96"
(1219 mm and 2438 mm) |
| 31/2" (89 mm) |
24" (610 mm) |
48" and 96"
(1219 mm and 2438 mm) |
| 4" (102 mm) |
24" (610 mm) |
48" and 96"
(1219 mm and 2438 mm) |
MADE-TO-ORDER SIZES
|
Thickness |
Width |
Length |
|
1" (25 mm)
|
24" to 48"
(610 mm to 1219 mm) |
48" and 96"
(1219 mm and 2438 mm) |
|
11/2" (38 mm)
|
24" to 48"
(610 mm to 1219 mm) |
48" and 96"
(1219 mm and 2438 mm) |
|
2" (51 mm)
|
24" to 48"
(610 mm to 1219 mm) |
48" and 96"
(1219 mm and 2438 mm) |
|
21/2" (64 mm)
|
24" to 48"
(610 mm to 1219 mm) |
48" and 96"
(1219 mm and 2438 mm) |
|
3" (76 mm)
|
24" to 48"
(610 mm to 1219 mm) |
48" and 96"
(1219 mm and 2438 mm) |
|
31/2" (89 mm)
|
24" to 48"
(610 mm to 1219 mm) |
48" and 96"
(1219 mm and 2438 mm) |
|
4" (102 mm)
|
24" to 48"
(610 mm to 1219 mm) |
48" and 96"